HVAC Engineer LabClarity in every calculation.
TOOL-001 · Engineering Mode · V1.0

Cooling & Heating Load Planner

Estimate peak cooling and heating demand with explicit design inputs, traceable rules, pinned sources and a report generated from the same Structured Result used by the UI.

Estimator scope: L1/L2 design-point engineering estimator. No hidden U-values, solar, gains, airflow, humidity or sizing margin defaults are applied.
Result units
Engineering inputs

Design conditions & loads

Canonical SI input
Project / zone
Indoor design
Outdoor design
Envelope surfaces
Surface 1
Fenestration / solar

Solar is intentionally not calculated unless SHGC, design irradiance and external shade factor are all explicit.

Glazing 1
Internal gains
Outdoor air & infiltration
Options
No hidden engineering defaults are injected.

Formulas, source and scope

Conduction q = U·A·(T_adjacent − T_indoor); cooling demand keeps the positive part and heating demand keeps the positive reverse. People gain = count × per-person sensible/latent × diversity. Lighting and equipment use the entered power × use factor. Solar, only when SHGC, irradiance and shade are all present: q = A·SHGC·I·shade. Outdoor-air cooling uses dry-air mass flow × moist-air enthalpy difference from the pinned PsychroLib adapter; sensible split uses (1006 + W·1860)·ΔT, with 1006 and 1860 as engine constants J/(kg·K). Sized load = base × (1 + margin%/100).

Pinned in this repo: PsychroLib 2.5.0 (SRC-PSYCHROLIB-2.5.0), EnergyPlus Engineering Reference 26.1.0 (SRC-ENERGYPLUS-ENGREF-26.1), project method V1.0 (SRC-PROJECT-METHOD-001). These pins are implementation and cross-check records, not a claim of code certification.

FAQ

Does a result certify a code load calculation?

No. It is an L1/L2 design-point estimate with explicit inputs. Confirm climate, schedules and construction data before design use.

Where is a reproducible case?

Use Load reviewed example, then Calculate. The same structured result feeds the on-page breakdown and the print report.